Copeland Digital Scroll Compressors




Get a Free Compressor Troubleshooting Guide – https://offers.refrigerationmentor.com/free-guide

Digital capacity control is achieved by axially separating the scroll members. During the time the members are separated, there is no gas compression and approximately 10% power usage. By varying the amount of time the members are separated, capacity control between 10 and 100% can be achieved. The separation is achieved by bypassing a controlled amount of discharge gas to the suction side through a solenoid valve. The lowering of the pressure in the modulating chamber allows the scrolls to separate and as a result, no pumping action takes place

Digital Capacity Control for Copeland Scrollâ„¢ Refrigeration Compressors
– https://webapps.emerson.com/online-product-information/Publication/LaunchPDF?Index=aeb&PDF=ae1319.pdf

HVAC Know it all digital chat – https://open.spotify.com/episode/3zNDfZFLINdb4a8rCCBu5E?si=-Frr0PlUQtWooQIxZbrOYg&dl_branch=1

HVACR School Podcast – https://open.spotify.com/episode/1Z0EYTqWI1xYUGQ992TPzT?si=cp_EJ1VjSOSLWcuqFSlYgA&dl_branch=1